CVE-2021-22681

Rockwell Multiple Products: Insufficient Protected Credentials

As of , CVE-2021-22681 in Rockwell Multiple Products is on CISA's list of exploited vulnerabilities: CISA listed it on . Our patch-first group: Patch this week.

Exploited
Yes: CISA listed it on 5 March 2026
US federal deadline
26 March 202621 days after CISA listed it. US federal civilian agencies must fix it by then.
Used in ransomware campaigns
Not known to CISA
EPSS score
0.64Higher than 99% of the CVEs EPSS scores. EPSS estimates the chance of exploitation activity in the next 30 days.
Public exploit
None foundNeither Metasploit nor Exploit-DB lists one.
Fix
Vendor advice: support.rockwellautomation.comLinks below, from CISA's entry.

What CISA says to do

Apply mitigations per vendor instructions, follow applicable BOD 22-01 guidance for cloud services, or discontinue use of the product if mitigations are unavailable.

CISA's required action

What the flaw is

Multiple Rockwell products contain an insufficient protected credentials vulnerability. Studio 5000 Logix Designer software may allow a key to be discovered. This key is used to verify Logix controllers are communicating with Rockwell Automation design software. If successfully exploited, this vulnerability could allow an unauthorized application to connect with Logix controllers. To leverage this vulnerability, an unauthorized user would require network access to the controller.

CISA's description

Rockwell Automation Studio 5000 Logix Designer Versions 21 and later, and RSLogix 5000 Versions 16 through 20 use a key to verify Logix controllers are communicating with Rockwell Automation CompactLogix 1768, 1769, 5370, 5380, 5480: ControlLogix 5550, 5560, 5570, 5580; DriveLogix 5560, 5730, 1794-L34; Compact GuardLogix 5370, 5380; GuardLogix 5570, 5580; SoftLogix 5800. Rockwell Automation Studio 5000 Logix Designer Versions 21 and later and RSLogix 5000: Versions 16 through 20 are vulnerable because an unauthenticated attacker could bypass this verification mechanism and authenticate with Rockwell Automation CompactLogix 1768, 1769, 5370, 5380, 5480: ControlLogix 5550, 5560, 5570, 5580; DriveLogix 5560, 5730, 1794-L34; Compact GuardLogix 5370, 5380; GuardLogix 5570, 5580; SoftLogix 5800.

The CVE record's description, from icscert

CVE published
3 March 2021
Assigned by
icscert
CVSS
9.8 Critical (CVSS 3.1, from CISA-ADP)
CWE-522
Insufficiently Protected Credentials
CISA SSVC, exploitation
active
CISA SSVC, automatable
yes
CISA SSVC, technical impact
total

Timeline

  1. The CVE record was published.
  2. CISA added it to its list of exploited vulnerabilities.
  3. The US federal deadline to fix it.

Read further